Master Programming Level

Programming

EDIT DETECTOR 1=ENABLED 2=TYPE

3=VERIFICATION

Edit Detector Screen #2

The following examples show the editing of a photoelectric smoke detector with address 017, located on the SLC loop:

EDIT DETECTOR 1D0171=ENABLED YES 2=TYPE SMOKE(PHOTO) 3=VERIFICATION OFFEdit Detector Screen #2

EDIT DETECTOR 1D017

1=WALKTEST NO2=PASNO3=PRE-SIGNAL NOEdit Detector Screen #3EDIT DETECTOR 1D017 1=ZONE ASSIGNMENT00 ** ** ** **Edit Detector Screen #4EDIT DETECTOR 1D017 1=NOUN/ADJECTIVE 2=DESCRIPTION

********************

Edit Detector Screen #5Enable/Disable Detector

To Enable or Disable the detector, press the 1 key while viewing the Edit Detector Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the detector will not be polled by the control panel, preventing the detector from reporting alarms and troubles to the panel. The control panel will display the device type and address which has been disabled and will turn on the Trouble LED and Disable LED.

MS-9200UDLS PN 52750:A 11/04/05

51