Programming

PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP

Programming Screen #2

Master Programming Level

detectors and 99 control/monitor modules. Newer devices can be set to addresses higher than 99 but these addresses will not function with the MS-9200UDLS.

Note that It is permissible to mix old and new devices on the same loop but the FACP must be set for CLIP mode when older devices are installed.

3.6.5 System Setup

System Setup allows the programmer to configure the following control panel features:

Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or trouble still exists on the FACP after the control panel has been silenced. The control panel piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will continue to sound at these rates until the alarm or trouble condition is cleared. If the trouble condition is not cleared within 24 hours, the panel will reactivate the trouble sounder and retransmit the trouble condition to the central station if connected.

Banner: This option allows the user to change the top two lines of the LCD display from the factory default readout of HONEYWELL LIFE SAFETY to a user defined readout when the control panel is in Normal condition.

Time-Date:This feature allows the programmer to set the time, display format (24 hr or 12 hr), date and daylight savings time feature into the FACP memory

Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time delay, Pre-Signal time delay and Waterflow time delay.

NACs: This feature allows the programmer to configure the control panel Notification Appliance Circuits for a variety of options, such as circuit type, silenceable/nonsilenceable, autosilence, coding, silence inhibit, zone assignment and enable/disable.

Relays: This option allows programming of two onboard relays for activation by various control panel events, such as alarm, trouble, supervisory, etc.

Canadian Option: This option allows the automatic programming of ionization smoke detector sensitivity thresholds to Canadian specifications.

Waterflow Silenceable: This option provides the ability to silence any output circuit activated by a monitor module programmed as a waterflow type.

Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following screens to be displayed:

SYSTEM SETUP1=TROUBLE REM OFF 2=BANNER 3=TIME-DATESystem Setup Screen #1SYSTEM SETUP 1=TIMERS2=NAC3=RELAYSSystem Setup Screen #2SYSTEM SETUP 1=CANADIAN OPT. OFF 2=WATERFLOW SIL. NOSystem Setup Screen #3