Read Status

READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER

Read Status Screen #1

Operating Instructions

4.22.1 System Point

Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed:

READ SYSTEM POINT

SELECT TYPE 1=DETECTOR 2=MODULE

The operator selects the type of device which is to be viewed by pressing 1 for Detector or 2 for Module. If 1 is pressed, the display will change to the following screen:

READ SYSTEM POINT

ENTER DETECTOR#

***

Entering the three digit detector address will cause the control panel to display the current status of the selected device. For example, if a detector with address 001 on the SLC loop is entered, a display similar to the following will appear:

NORMAL SMOKE(PHOTO)NORTH CLASSROOMZ005V 1D001

The information in the preceding display includes:

NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)

SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be ION for ionization smoke detector)

NORTH CLASSROOM - the Adjective/Noun label for this device

Z005 - the first of five possible assigned software zones

1D001 - 1 = SLC Loop, D = Detector, 001 = Address 001

V - Alarm Verification Enabled (V = Yes, * = No)

S - Silenceable for control modules (S = Yes, * = No)

W - Walktestable for control and monitor modules (W = Yes, * = No)

MS-9200UDLS PN 52750:A 11/04/05