Read Status
READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER
Read Status Screen #1
Operating Instructions
4.22.1 System PointPressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed:
READ SYSTEM POINTSELECT TYPE 1=DETECTOR 2=MODULE
The operator selects the type of device which is to be viewed by pressing 1 for Detector or 2 for Module. If 1 is pressed, the display will change to the following screen:
READ SYSTEM POINT
ENTER DETECTOR#
***
Entering the three digit detector address will cause the control panel to display the current status of the selected device. For example, if a detector with address 001 on the SLC loop is entered, a display similar to the following will appear:
NORMAL SMOKE(PHOTO)NORTH CLASSROOMZ005V 1D001The information in the preceding display includes:
•NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)
•SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be ION for ionization smoke detector)
•NORTH CLASSROOM - the Adjective/Noun label for this device
•Z005 - the first of five possible assigned software zones
•1D001 - 1 = SLC Loop, D = Detector, 001 = Address 001
•V - Alarm Verification Enabled (V = Yes, * = No)
•S - Silenceable for control modules (S = Yes, * = No)
•W - Walktestable for control and monitor modules (W = Yes, * = No)