Operating Instructions
READ STATUS 1=SYSTEM POINT 2=ZONES 3=POWER
Read Status Screen #1
Read Status
Pressing the down arrow key, while viewing the screen shown above, will allow the operator to view additional programming information about the selected device, such as:
•Enable/Disable Status
•Device Type
•Alarm Verification On/Off (for detectors)
•Walktest Yes/No
•PAS (Positive Alarm Sequence) Yes/No (for detectors only)
•
•Zone Assignments (five maximum)
•Chamber Reading
•Adjective/Noun descriptor
•Silenceable Yes/No (for control modules)
4.22.2 ZonesPressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed:
ZONES1=ZONES INSTALLED 2=ZONES ENABLED 3=ZONES DISABLED
Zones Screen #1ZONES
1=SPECIAL PURPOSE 2=ZONE TYPE 3=ZONE MESSAGEZones Screen #2From the preceding screens, the control panel operator can view:
•Zones Installed - all software zones programmed into the system (99 maximum)
•Zones Enabled - all software zones that are enabled
•Zones Disabled - all software zones that have been disabled
•Special Purpose - on or off programming for Special Purpose Zones 97 reserved for PAS, 98 reserved for
•Zone Type - the Type assigned to each installed zone (default is Alarm)
•Zone Message - the Message assigned to each installed zone
142 |