Master Programming Level

Programming

If an ACS annunciator is installed, press 1 while viewing Annunciator Screen #2 to select addresses for the ACS annunciators. The following screen will be displayed:

OPTION MODULES

1=ANNUNCIATORS/UDACT 2=ON BOARD DACT 3=PRINTER/PC

Option Module Screen

ANNUNCIATOR

 

1=ADDRESS 1

YES

2=ADDRESS

2

NO

3=ADDRESS

3

NO

ACS Installed Screen

Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1 -31. To select one or more addresses for the installed ACS annunciator(s), press the number key corresponding to the address in each screen.

The display for the selected address will change from No to Yes. Each press of the number key will cause the display to toggle between No and Yes.

3.6.9.2 Onboard DACT

The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a central station. Pressing 2 while viewing the Option Module Screen will cause the following screens to be displayed:

ON BOARD DACT

1=ENABLED YES 2=PRIMARY PHONE 3=SECONDARY PHONE

On Board DACT Screen #1

ON BOARD DACT 1=SERVICE TERMINAL 2=CENTRAL STATION 3=MANUAL DIAL MODE

On Board DACT Screen #2

3.6.9.2.1 Onboard DACT Enable

To enable the onboard DACT, press 1 while viewing Onboard DACT Screen #1 until the display reads Enabled Yes. The display will toggle between Enabled Yes and Enabled No with each press of the key.

MS-9200UDLS PN 52750:A 11/04/05

97