Master Programming Level | Programming |
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
Programming Screen #1
Pressing 1 while viewing Programming Screen #1, will select the Autoprogram option, which prompts the control panel to poll all devices installed on the SLC loop. The primary purpose of autoprogramming is to allow the installer a fast and easy way to bring the system
If the system is already programmed and Autoprogram is initiated, the system will only add default values for newly installed devices.
When Autoprogram is selected, the control panel will begin autoprogramming the system by communicating with each addressable device installed on the SLC loop. While autoprogramming, the panel will display the following:
AUTOPROGRAMAUTOPROGRAMMING!PLEASE WAITAutoprogram Progress ScreenWhen Autoprogramming is completed, the control panel will display the type and quantity of each device installed on the SLC loop similar to the following display:
#OF DET LOOP1 055#OF MON LOOP1 035#OF CON LOOP1 030Autoprogram Result Screen #1In the preceding example, the display indicates that the SLC Loop has 55 addressable detectors, 35 monitor modules and 30 control modules installed.
Pressing the ESC key will return the display to Programming Screen #1.
47 |