Programming | Master Programming Level |
SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS
System Setup Screen #2
3.6.5.6 Relays
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to configure two of the three main circuit board
RELAYS
1=RELAY 1 2=RELAY 2 3=RELAY 3
Relays Selection Screen
To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no effect on its programming. The following screen will appear for each relay to be programmed:
RELAY # 1=TYPE
ALARM
Relay Type Screen
Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be displayed:
RELAY
1=ALARM
2=SUPERVISORY 3=SUPERVISORY AR
Relay Screen #1
RELAY 1=TROUBLE 2=COMM FAIL 3=PROCESS-MON
Relay Screen #2
RELAY
1=PROCMON AR 2=AC LOSS 3=HAZARD
Relay Screen #3
RELAY 1=MEDICAL
Relay Screen #4
While viewing the selected screen, press the number corresponding to the desired relay type to program the main circuit board relay. The choice will be stored in memory and the display will return to the Relay Type Screen which will show the programmed type choice. Press the Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
Note: AR in SUPERVISORY AR and PROCMON AR indicates AutoResettable which means that the relay will not latch when either of these conditions occur. If the corresponding condition is cleared, the relay will return to its normal state without the necessity of resetting the control panel.