Installation | Relays |
2.4 Relays
The FACP provides two programmable
Note that relay connections may be
Note that the programmable relay labeled as Relay 1 is factory default programmed as Alarm and programmable Relay 3 is factory default programmed as Supervisory.
The relay labeled Relay 2 is fixed as a Trouble relay and cannot be changed. It is a
RELAY 3 |
| RELAY 1 |
| RELAY 2 |
|
|
|
|
|
NO NC C |
| NO NC C |
| NO NC C |
|
|
|
|
|
92udreyp.cdr
Relay contacts shown with power applied to panel and no active troubles, alarms or supervisories
Figure 2.6 Relay Terminals2.5 Notification Appliance Circuits
See Page
Reference
Manual
The control panel provides four Style Y (Class B) or two Style Z (Class A) NACs (Notification Appliance Circuits). Each circuit is capable of 2.5 amps of current. Total current in alarm for all external devices cannot exceed 6.0 amps (refer to "Calculating the System Current Draw" on page 164). Use UL listed 24 VDC notification appliances only. Circuits are supervised and
The following sections describe the configuration and wiring of Style Y and Style Z Notification Appliance Circuits on the