Specifications

Product Description

EIA-485 (TERM) or EIA-232 (ACS) - TB8

EIA-485 Terminal Mode annunciator connections: Terminal 1 (Out +), 2 (In +), 3 (Out -), 4 (In -)

EIA-232 PC/Printer applications connections: Terminal 1 (Transmit), 2 (Receive), 3 (Ground)

EIA-485 (ACS) - TB9

ACS annunciator connector, Terminal 1 (+) and Terminal 2 (-), requires ferrite bead

1.2.1 Current Availability

The following figure illustrates the maximum current that is possible for each panel circuit and the total current available from the FACP with optional second transformer.

Note: If NACs are configured as two Style Z (Class A) circuits, each circuit can handle 2.5 amps maximum.

Refer to the battery calculations section for additional information.

Figure 1.1 Current Availability

6.0amps with optional second XRM-24(E) transformer.

3.0amps max. with only standard transformer installed.

owerdist9200ud.cdr

MS-9200UDLS PN 52750:A 11/04/05

15