Operating Instructions | Read Status |
READ STATUS
1=SERVICE TERMINAL 2=PRINTER/PC 3=PRINT
Read Status Screen #5
To print program data or control panel status, press 3 while viewing Read Status Screen #5. The following screens will be displayed:
PRINT1=HISTORY2=WALKTEST LOG 3=DETECTOR DATAPrint Screen #1
Print Screen #2
Pressing 1 while viewing Print Screen #1 allows the user to print the History file which will detail all of the system activities since the file was last cleared from memory.
Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log which will detail all of the system activations during walktest since the log was last cleared. Refer to "Walktest" on page 95 for additional information on the display.
Pressing 3 while viewing Print Screen #1 allows the user to print the detector data for each addressable smoke detector connected to the system. A printout, similar to the following example, will be generated if an optional printer is connected to the FACP.
DEVICE# | DEVICE TYPE | %DRIFT COMP | CHAMBER | TIME/DATE |
1D001 | SMOKE (PHOTO) | 20 | 1281 | 12:01AM |
1D002 | SMOKE (PHOTO) | 20 | 1281 | 12:01AM |
1D003 | SMOKE (PHOTO) | 21 | 1259 | 12:01AM |
1D004 | SMOKE (PHOTO) | 20 | 1309 | 12:02AM |
1D005 | SMOKE (PHOTO) | 21 | 1281 | 12:02AM |
1D006 | SMOKE (PHOTO) | 20 | 1322 | 12:02AM |
1D007 | SMOKE (PHOTO) | 20 | 1280 | 12:02AM |
1D008 | SMOKE (PHOTO) | 20 | 1215 | 12:02AM |
1D009 | SMOKE (PHOTO) | 20 | 1310 | 12:02AM |
The Chamber value should be within the indicated range for the following smoke detectors:
•SD350(T), D350P(R) and SD300(T) Addressable Photoelectric Smoke Detectors: 405 - 2100 (obscuration of 1.00%/ft to 3.66%/ft.)
•CP350 and CP300 Addressable Ionization Smoke Detectors: 750 - 2100 (obscuration of 0.50%/ft. to 1.44%/ft.)
If the addressable smoke detector’s Chamber reading is not within the acceptable range, clean the detector and check the Chamber value again. If the reading is still not within the acceptable range, immediately replace the detector.
150 |