The following steps must be followed when installing the 4XTMF module:
1. Remove all power (Primary and Secondary) from the FACP before installing 4XTMF
2.Cut jumper JP3 on the main circuit board to allow the control panel to supervise the 4XTMF module
3.Carefully plug the connectors on the 4XTMF module into connectors J5 and J6 on the
4.Secure 4XTMF module to standoffs with supplied screws.
5.Reapply power to the FACP
6.For proper 4XTMF operation, the output relays must be programmed for the factory default settings: Alarm Relay 1, Trouble Relay 2 and Supervisory Relay 3
7.When the installation has been complete, enable the 4XTMF module by sliding the disconnect switch to the left
8.Test system for proper operation