Programming | Master Programming Level |
The programmer can select the notification appliance output by pressing the number corresponding to the desired output. The coding selections are:
•Steady - a continuous output with no coding
•March Time - 120 ppm
•California - 10 seconds on and 5 seconds off
•Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second off
•Two Stage - refer to "Two Stage Operation" on page 90 for a description
Selection of one of the above options will cause the control panel to store the information in memory and return the display to NAC Screen #2, which will display the new coding choice.
3.6.5.5.5.1 Two Stage OperationTwo Stage operation consists of the following:
•1st stage output - 20 ppm
•2nd stage output - Temporal coding as described above
If Two Stage operation is programmed as the Coding option, the following sequence of events will occur during an alarm.
1.The
2.If the activated alarm point is directly mapped to a zone which is programmed to an
3.If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has not been pressed, all NACs presently in 1st stage activation will go to 2nd stage activation
4.If an Acknowledge switch has been pressed, any NACs currently in 1st stage activation will remain in 1st stage. Pressing the Acknowledge switch does not affect NACs already in 2nd stage activation
5.If another alarm point is activated and the countdown timer is counting, the alarm point will have no effect on the NACs unless the alarm point’s zones are directly mapped to one of the NACs, in which case it will follow the procedure outlined in step 2
6.If another alarm point is activated and the countdown timer has stopped counting due to the Acknowledge switch being pressed, the countdown timer will restart and the NACs will respond as outlined in step 2. NACs already in 2nd stage activation will not be affected
7.Any control modules assigned to special Zone 99 will be activated either by direct mapping of an input device programmed to Zone 99 or if the timer counts down to zero
8.Control modules that are programmed to the same zone as the activated input device will not be delayed for activation