Programming

EDIT CONTROL 1=ENABLED 2=TYPE

3=SILENCEABLE

Edit Control Screen #2

Master Programming Level

Type

To select the type of control module being programmed, press the 2 key while viewing the Edit Control Screen #2. This will cause the control panel to display the following Control Type Screens. Press the down arrow key to view additional screens and selections.

CONTROL TYPE 1=BLANK 2=BELL-CIRCUIT 3=HORN-CIRCUITControl Type Screen #1

While viewing one of the Control Type screens, select the type of control module being programmed by pressing the corresponding keypad number key. The display will return to the Edit Control Screen #2 and indicate the new type selection.

Note: A control module set to the Resettable Power type will follow the main circuit board 24 VDC resettable power unless the control module is disabled.

The following table contains control module type codes and their functions which are displayed in the Control Type screens:

Control Type

Special Function

Blank

None

 

 

Bell Circuit

None

 

 

Horn Circuit

None

 

 

Sounders

None

 

 

Relay

Ignore Open Circuit

 

 

Strobe Circuit

None

 

 

Control

None

 

 

Resettable Power

Relay Type - Ignore Open Circuit

 

 

HVAC SHUTDN

Relay Type - Ignore Open Circuit

 

 

Note: For HVAC SHUTDN description, refer to "Control Module Operation" on page 179

70

MS-9200UDLS PN 52750:A 11/04/05