Programming | Master Programming Level |
The information shown in Table 3.4 is automatically programmed for the Central
Station phone number Event Codes when Ademco Contact ID Format is selected.
Enter 000 for an Event Code Setting to disable the report.
| Table 3.4 Event Codes |
|
|
Event Description | Event Code Settings |
| Active |
|
|
PULL STATION | 115 |
115 | |
WATERFLOW | 113 |
113 | |
SMOKE (PHOTO) | 111 |
111 | |
SMOKE (ION) | 111 |
111 | |
HEAT DETECT | 114 |
114 | |
SMOKE | 116 |
116 | |
DUCT SUPERVISORY | 200 |
200 | |
not used | 000 |
not used | 000 |
not used | 000 |
not used | 000 |
MONITOR | 110 |
110 | |
not used | 000 |
not used | 000 |
SMOKE CONVEN | 111 |
111 | |
HEAT DETECT | 114 |
114 | |
MEDIC ALERT | 100 |
100 | |
HAZARD ALERT | 150 |
150 | |
TORNADO ALRT | 150 |
150 | |
not used | 000 |
not used | 000 |
TAMPER | 144 |
144 | |
MON SUPERVISORY | 200 |
200 | |
MON SUPERV AUTO | 200 |
200 | |
POWER MON | 330 |
330 | |
TROUBLE MON | POINT_FAULT code will always be transmitted |
POINT_FAULT code will always be transmitted | |
PROCESS MON | 000 |
112 |