Wire Requirements
APPENDIX D
Correlations
Wire Requirements
Connecting external system accessories to the
Note: If the SLC loop is to be run in conduit with Notification Appliance Circuits, the risk of encountering problems can be greatly reduced by exclusively employing electronic sounders (such as
CIRCUIT CONNECTIONS |
| WIRE REQUIREMENTS | ||
|
|
|
|
|
|
|
| Recommended |
|
Circuit Type | Circuit Function | Wire Type and Limitations | Max. Distance | Wire Gauge and Compatible Brands |
|
|
| Feet (meters) |
|
|
|
|
|
|
SLC loop | Connects to | Twisted pair, 40 ohms | 10,000 (3,000 m) | 12 AWG (3.1 mm2): Genesis |
Addressable | maximum per length of |
| ||
| Devices | Style 6 and 7 loops. 40 | 8,000 (2,400 m) | 14 AWG (2.00 mm2):Genesis |
|
| ohms per branch maximum |
| |
|
| for Style 4 loops1 |
| |
|
| 4,875 (1,450 m) | 2 | |
|
|
| 16 AWG (1.30 mm ): Genesis | |
|
|
|
| |
|
|
| 3,225 (980 m) | 18 AWG (0.78 mm2): Genesis |
|
|
|
| |
|
| Untwisted, unshielded pair | 3,000 (900 m) | |
ACS/TERM | Connects to | Twisted, shielded pair with a | 6,000 (1,800 m) | 18 AWG (0.75 mm2) |
annunciator | characteristic impedance of |
|
| |
modules | 120 ohms |
|
| |
connects to | Twisted, shielded pair | 50 (15 m) | 18 AWG (0.75 mm2) minimum | |
remote printer |
|
|
| |
| and PC computer |
|
|
|
Initiating Device | Maximum loop wire | 2,500 (760 m) | ||
Circuit | resistance is 40 ohms for the |
|
| |
|
|
| ||
|
| the |
|
|
Initiating Device | No more than a 2.4 volt drop | 2,500 (760 m) | ||
Circuit | allowed at end of circuit. |
|
| |
|
| Maximum loop wire |
|
|
|
| resistance is 25 ohms |
|
|
Notification | In alarm, no more than a 1.2 | Distance limitation | ||
Appliance | volt drop allowed at end of | set by 1.2 volt |
| |
| Circuit | circuit | maximum line |
|
|
|
| drop |
|
24 VDC | Connects to | No more than 1.2 volt drop | Distance limitation | |
filtered | allowed from supply source | set by 1.2 volt |
| |
resettable | detectors | to end of any branch | maximum line |
|
|
| drop |
| |
24 VDC | Connects to | No more than 1.2 volt drop | Distance limitation | |
nonresettable | control modules, | allowed from supply source | set by 1.2 volt |
|
annunciators and | to end of any branch | maximum line |
| |
| accessories |
| drop |
|
Remote | 12 AWG (3.25 mm2) in | 20 (6 m) | ||
secondary power | conduit |
|
| |
| source |
|
|
|
Table Footnote |
|
|
|
|
1. When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.