Programming

Maintenance Programming Level

Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be displayed:

ZONES NO OUTPUT

05 07 09 10 11 1D001

PROGRAMMING 1=WALKTEST 2=SYSTEM

3=ZONE SETUP

Maintenance Screen #2

The Zone No Output feature allows the programmer to view the zones which have not been programmed to at least one output device (not including general alarm Zone 00). The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an addressable detector with an address of 001 on loop 1 but have not been programmed to any output devices. Use the up and down arrow keys to view all the zones without output assignments.

3.7.4 Walktest

To perform a walktest, press 1 while viewing Maintenance Screen #2. The following screen will be displayed:

WALKTEST

1=SILENT

2=AUDIBLE

3=VIEW RESULT

Walktest Screen

The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. The display will read UNIT IN WALKTEST. To end the Walktest, press the Esc (Escape) key.

Pressing 3 after the walktest has been completed, will allow the operator to view the results of the walktest.

3.7.5 System

To program the time and date into the control panel, press 2 while viewing Maintenance Screen #2. The following display will appear:

SYSTEMS 1=TIME/DATESystem Screen

124