Programming | Maintenance Programming Level |
Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be displayed:
ZONES NO OUTPUT
05 07 09 10 11 1D001
PROGRAMMING 1=WALKTEST 2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
The Zone No Output feature allows the programmer to view the zones which have not been programmed to at least one output device (not including general alarm Zone 00). The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an addressable detector with an address of 001 on loop 1 but have not been programmed to any output devices. Use the up and down arrow keys to view all the zones without output assignments.
3.7.4 WalktestTo perform a walktest, press 1 while viewing Maintenance Screen #2. The following screen will be displayed:
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Walktest Screen
The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. The display will read UNIT IN WALKTEST. To end the Walktest, press the Esc (Escape) key.
Pressing 3 after the walktest has been completed, will allow the operator to view the results of the walktest.
3.7.5 SystemTo program the time and date into the control panel, press 2 while viewing Maintenance Screen #2. The following display will appear:
SYSTEMS 1=TIME/DATESystem Screen124 |