Programming
EDIT MONITOR
Edit Monitor Screen #3
See Page
EDIT MONITOR 1=WALKTEST
2=ZONE ASSIGNMENT 00 ** ** ** **
Edit Monitor Screen #4
EDIT MONITOR 1=NOUN/ADJECTIVE 2=DESCRIPTION
*****************
Edit Monitor Screen #5
Master Programming Level
To enable the
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel after each device activation. To enable devices, which are connected to a monitor module, for the Walktest feature, press 1 while viewing the Edit Monitor Screen #4 until the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 139 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2 while viewing Edit Monitor Screen #4 displays the following screen:
MON ZONE ASSIGNZ00 Z** Z** Z** Z**
Zone Assignment Screen
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this device. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zones Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the Edit Monitor Screen #4.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the monitor module currently being programmed. Pressing 1 while viewing Edit Monitor Screen #5 will cause the following screen to be displayed:
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen