Specifications

Introduction

The following tables contain electrical, physical, safety and performance specifications for the UMC800 controller.

Controller Design

Parameter

Controller

Description

CPU with two serial communication ports,* power supply, and backplane assembly. Capable of supporting up to 16 input /output modules.

*CPU option provides additional RS 485 communications with Modbus RTU protocol.

I/O Module Configuration

Component

Universal Analog Inputs

(Module ID 1)

Parameter

Input Types

Number of Inputs

Signal Source

Input Impedance

Input Isolation

Stray Rejection

Burnout

Description

mV, V, mA, T/C, RTD, Ohms

4 per module, up to 16 modules per controller (64 inputs)

Thermocouple with cold junction compensation Line resistance up to 1000 ohms, T/C, mV, mA, V

RTD Pt 100 ohms, 3-wire connections, 40 ohms balanced maximum

10 megohms for T/C and mV inputs; >1 megohm for volt inputs

400 Vdc point-to-point

3.75K Vac RMS A/D converter to logic

Series mode >60 dB. Common mode at 120 Vac >130 dB.

T/C, mV, V (except following ranges) configurable to upscale, downscale, or none.

Volt: –500 mV to 500 mV; –1 V to 1 V; –2 V to 2 V; –5 V to 5 V; 0 V to 10 V; –10 V to 10 V; inherent to zero volt

RTD: Inherent upscale

mA: Inherent downscale

T/C Break Detection

Via current pulse

Release E

UMC800 Controller Installation and User Guide

93

4/01

 

 

Page 101
Image 101
Honeywell UMC800 manual Specifications, Controller Design, Module Configuration