Maintenance

Controller Calibration

Factory calibration

Factory calibration of controller components is performed before shipment to 0.1% accuracy. Calibration values are contained in a number of the controller components, namely: the CPU, Backplane, and AI and AO modules.

Figure 32 shows the various components in which calibration data is stored.

Calibration functions and parameters for the user interface are stored in memory on the CPU.

Each AI module contains two (2) cold junction compensation (CJC) references that are factory calibrated. Factory calibration data for the CJC references is stored in a non-volatile memory on the AI module.

Field calibration values for the AI modules (both zero offset and span calibration and CJC reference values) are stored on the CPU.

Factory calibration values (zero offset and span corrections) for AO modules are stored in non-volatile memory on the AO module and can be changed only if the write protect jumper is not cut. See Write Protect Jumper ST1.

The gains and offsets of the preamp are factory calibrated and the calibration data is stored in a non- volatile memory on the backplane. No field calibration of these values is possible.

Write Protect Jumper ST1

ATTENTION

A jumper (ST1) on the AO module PWA can be cut to prevent changes to calibration values. This will write protect the AO and prevent further calibration of these values.

 

AI Module

CPU

 

 

 

 

AI01

CJC

Field

Calibration

 

Function

AI02

Calibration

CJC Factory

 

Values

 

 

Calibration

 

AI03

(AI and CJC)

 

Values

Calibration

in Battery-backed RAM

 

CJC

User Interface

AI04

 

 

 

 

AO Module

AO01

ST1

Backplane

AO02

Factory

 

& Field

Factory Calibrated

 

AO03

Calibration

Preamp Gains and Offsets

Values

(for AI and CJC)

 

AO04

 

 

Figure 32 Controller components that contain calibration values

66

UMC800 Controller Installation and User Guide

Release F

 

 

4/01