Diagnostics and Troubleshooting

Fault Detection and Troubleclearing

Fault detection and troubleclearing

Table 21 describes the status messages that appear on the I/O Module Diagnostics displays in the user utility and operator interface, as well as the status indications of the POWER LED located on the controller CPU module.

Table 21 Details of the I/O module diagnostics display

I/O Module

Diagnostics

(In The User Utility and

Operator Interface)

Menu

Status

Item

 

 

 

MODULE

GOOD

1through

MODULE

Controller

 

Fault Detection / Troubleclearing

LED on CPU

 

 

 

 

 

 

 

 

 

 

 

Possible Cause

Controller Action

User Action

 

 

 

 

 

 

 

 

 

 

 

MODULE

HI CJ

1 through

TEMPERATURE

MODULE

 

16

 

 

 

MODULE

WRONG

1 through

MODULE

MODULE

 

16

 

 

 

MODULE NO MODULE

1through

MODULE

POWER LED flashes 10 times

POWER LED flashes 11 times

POWER LED flashes 11 times.

High cold junction temperature on AI module.

The module does not agree with the module required for the control strategy.

No module found in the slot that requires a module for the control strategy.

Executes normally.

These function block types do the following:

AI – sets its output to failsafe

DI – sets its output to OFF

These function block types do the following:

AI – sets its output to failsafe

DI – sets its output to OFF

1.Improve ventilation to rack.

2.Replace AI module

1.Replace module.

2.Check configuration.

1.Install the correct type of module.

2.Check configuration.

Release F

UMC800 Controller Installation and User Guide

87

4/01

 

 

Page 95
Image 95
Honeywell UMC800 Fault detection and troubleclearing, Details of the I/O module diagnostics display, Module Diagnostics