Maintenance

Controller Calibration

Controller Calibration

ATTENTION

All Analog Input (AI) and Analog Output (AO) modules are factory calibrated to 0.1% accuracy. If this accuracy is sufficient for your applications, there is not need to recalibrate the modules. If greater accuracy is required, the field calibration procedures will provide a 0.05% accuracy.

Please keep in mind that if you field calibrate AI or AO modules, you may have to recalibrate these modules after performing certain replacement procedures. [See Replacement Procedures (page 70).]

Calibration overview

Field Calibration of AI and AO modules in the controller is accomplished through either the operator interface or the user utility program.

Using the operator interface – Calibration displays are accessed from the UNIT SETUP display and provide menu selections and display prompts that guide you through the desired calibration procedure.

Using the user utility – Calibration dialog windows are accessed through menu selections in the Maintenance menu.

Analog Input modules can be calibrated to a number of references.

1.Calibration using 0% and 100% reference values applied at the terminal blocks of each module channel.

2.Copying calibration values from one module channel to another. For example, you can copy the calibration from one channel of a AI module to another channel of the same module, or to a channel of a different AI module.

3.Calibration of the cold junction compensation references.

4.Restoring factory calibration values.

Analog Output modules also can be calibrated using measured values from the channel outputs, or they can be restored to the initial factory calibration.

Release F

UMC800 Controller Installation and User Guide

65

4/01

 

 

Page 73
Image 73
Honeywell UMC800 manual Controller Calibration, Calibration overview