Specifications I/O Module Configuration

Component

Parameter

Description

Logic Inputs

(Module ID 3 and B)

Digital Outputs

Inputs per Module

Switching Voltage

Switching Current

Outputs per Module

Operating Voltage

Output Type

Peak Voltage

AC Frequency

ON Voltage Drop

Maximum Load Current

6 (ID 3) or 16 (ID B) dry contact

5Vdc

5mA

AC Outputs

(Module ID 8)

6

15 Vac to 240 Vac

SSR (Triac)

264 Vac

47 Hz to 63 Hz

<1.5 Vac (>0.1A) <3.0 Vac (<0.1A)

0.5 A per point or

2 outputs at 2.0 A and

4 outputs at 0.5 A

DC Outputs

(Module ID 7)

6 (current sinking)

10.2Vdc to 26.4 Vdc NPN open collector 40 Vdc

N/A

1.5Vdc maximum

0.3 A per point

Maximum Leakage Current

Maximum Inrush

Current

Minimum Load

Base Power required *

OFF to ON Response

ON to OFF response

Fuses

5 x 20mm

4 mA (240 Vac, 60 Hz)

1.2mA (100 Vac, 60 Hz)

0.9mA (100 Vac, 50 Hz)

10 A for 10 ms

10 mA

20 mA / ON pt. 250 mA maximum

1 ms

1 ms +1/2 cycle

1 per output, 1.5 A slow blow

0.1 mA @ 40 Vdc

1 A for 10 ms

0.5 mA

100 mA maximum

5V

1ms

1ms

1 per output

1 A fast blow

Release F

UMC800 Controller Installation and User Guide

95

4/01

 

 

Page 103
Image 103