Specifications
Environmental and Operating Conditions
Environmental and Operating Conditions
Parameter
Ambient Temp. °F °C
Ambient Relative Humidity *
Mechanical
Acceleration
Duration
Vibration
Reference
77 ± 5
25 ± 3
10 % to 55 % RH
0g
0ms
10 Hz to 60 Hz— amplitude 0.07 mm
60 Hz to 150 Hz— acceleration 1 g
Rated
32 to 131
0 to 55
10 % to 90 % RH
1g
30ms
0 Hz to 14 Hz— amplitude
2.5 mm
14 Hz to 250 Hz— acceleration 1 g
Extreme
32 to 140
0 to 60
5 % to 90 % RH
5g
30ms
Transportation
and Storage
5 % to 95 % RH
20g
30ms
*Relative Humidity is derated above 40 °C.