Mounting and Wiring
Signal Wiring
30 UMC800 Controller Installation and User Guide Release F
4/01
Digital outputsThere are four types of Digital Output (DO) modules that provide three types of Off/On control.1. Relay (alarm) output (Module ID 6) 46190308-5032. DC output (Module ID 7) 46190341-5013. AC output (Module ID 8) 46190344-5014. AC high output (Module ID A) 46190344-502Figure 17 shows the terminal block connections for the DC output and AC output DO modules. SeeSpecifications section for details on all I/O module specifications.
+
24V
-
Load
Field Wiring
Fuse
ModuleID #7
DCIOutput (24 Vdc)
12
11
10
9
8
7
6
5
4
3
2
1
DO 6
DO 4
DO 3
DO 1
DO 5
DO 2
Module ID
#6, 7, 8,
orA
Field Wiring
L1
L2 Load
ModuleID #6
Relay(Alarm) Output
VCC
L1
L2 Load
Fuse R
Field Wiring
ModuleID #8
AC Output(120/240 Vdc)
ModuleID A
AC Output(120/240V dc)
Wiring same as module 8.
Maximum Loa d Current :
Outputs
DO 1 4 @ .5A
DO 5 and 6 @ 2A
Figure 17 DO module terminal block connections