Equipment Identification
Serial Communication Ports
Serial Communication Ports
The controller contains dedicated serial ports for external communications. These are described in Table 2.
Communication
Port
(on CPU Module)
Configuration
Display
COMM A
(with optional
communication
board)
COMM B
(with optional
communication
board)
Table 2 Communication port descriptions
Description
Configuration Port - This RS232 port is a dedicated connection for communications with a PC running the Control Builder configuration program. The communications link layer protocol is proprietary. Communication is through a null modem cable or through a modem.
This RS 422 port is a dedicated connection for communications with the operator interface. Separate power leads included in the cable also supply power to the operator interface. The communications link layer is proprietary and not intended for external use.
RS 485 Serial communication port using Modbus RTU protocol. This port allows the controller to operate as a slave device on a
RS 485 Serial communication port using Modbus RTU protocol. This port allows the controller to operate as a master device to up to 16 slave Modbus compatible devices. Data transferred through this port is integrated into the user’s control strategy through read and write function blocks.
10 | UMC800 Controller Installation and User Guide | Release F |
|
| 4/01 |