Mounting and Wiring
Signal Wiring
Pulse frequency card outputs
The pulse frequency card outputs are open collector drivers designed to drive a maximum of 100 mA. All Pulse Frequency card digital outputs are optically isolated from each other. The maximum supply voltage must not exceed 27 Volts dc.
V Supply (DC) 27 V Max
IL (100mA Max)
+
V Return (DC)
+
Pulse / Frequency Input Card
DO connections
Figure 22 Pulse/frequency card digital output connections
Release F | UMC800 Controller Installation and User Guide | 35 |