Specifications Design
Design
Parameter
Scan Rate
Setpoint Programmers
Power Supply
Power Consumption
CPU Battery
Wiring
Communications
Description
1 AI module – (1 to 4 analog inputs): 333 milliseconds
2 AI modules – (5 to 8 analog inputs): 500 milliseconds
3 AI modules – (9 to 12 analog inputs): 700 milliseconds
4 AI modules – (13 to 16 analog inputs): 900 milliseconds
5 AI modules – (17 to 20 analog inputs): 1100 milliseconds
6 AI modules – (21 to 24 analog inputs): 1300 milliseconds
7 AI modules – (25 to 28 analog inputs): 1500 milliseconds
8 AI modules – (29 to 32 analog inputs): 1700 milliseconds
9 AI modules – (33 to 36 analog inputs): 1900 milliseconds
10 AI modules – (37 to 40 analog inputs): 2100 milliseconds
11 AI modules – (41 to 44 analog inputs): 2300 milliseconds
12 AI modules – (45 to 48 analog inputs): 2500 milliseconds
13 AI modules – (49 to 52 analog inputs): 2700 milliseconds
14 AI modules – (53 to 56 analog inputs): 2900 milliseconds
15 AI modules – (57 to 60 analog inputs): 3100 milliseconds
16 AI modules – (61 to 64 analog inputs): 3300 milliseconds
Scan rate dependent upon the number and type of configured function blocks.
Analog outputs will be updated at the same rate as analog inputs.
Fast Logic digital I/O will be serviced one time every 100 msec.
Up to four independent setpoint programs can be configured with up to 50 segments each. Up to 70 programs maximum storage.
Standard: 100 Vac to 240 Vac, 50 Hz or 60 Hz; or 100 Vdc to 240 Vdc
Fuse: 3.15 A T 250v, or equivalent.
Optional: 24 V dc or ac, 50 Hz or 60 Hz
Fuse: 6.3 A slow blow, or equivalent.
100 VA maximum
Lithium: Tadiran TL5101/SPD ½ AA, 3.6 Vdc
Removable terminal blocks with
Two ports for external connections –
CONFIGURATION: RS232 port dedicated connection of the controller to a PC running the Control Builder Configuration software.
DISPLAY: RS422 port dedicated connection to the Operator Interface.
Optional: Two RS 485 Serial Communication ports, Modbus® RTU Protocol, Ethernet protocol.
Connection: Twisted pair with shield.
Distance: 600 meters, (2000 feet)
Communication mode: Half duplex
Number of devices/link: COMM A: 31, COMM B: 16
Baud Rates: 9600, 19200, 38400
Release F | UMC800 Controller Installation and User Guide | 97 |