Specifications Design

Design

Parameter

Scan Rate

Setpoint Programmers

Power Supply

Power Consumption

CPU Battery

Wiring

Communications

Description

1 AI module – (1 to 4 analog inputs): 333 milliseconds

2 AI modules – (5 to 8 analog inputs): 500 milliseconds

3 AI modules – (9 to 12 analog inputs): 700 milliseconds

4 AI modules – (13 to 16 analog inputs): 900 milliseconds

5 AI modules – (17 to 20 analog inputs): 1100 milliseconds

6 AI modules – (21 to 24 analog inputs): 1300 milliseconds

7 AI modules – (25 to 28 analog inputs): 1500 milliseconds

8 AI modules – (29 to 32 analog inputs): 1700 milliseconds

9 AI modules – (33 to 36 analog inputs): 1900 milliseconds

10 AI modules – (37 to 40 analog inputs): 2100 milliseconds

11 AI modules – (41 to 44 analog inputs): 2300 milliseconds

12 AI modules – (45 to 48 analog inputs): 2500 milliseconds

13 AI modules – (49 to 52 analog inputs): 2700 milliseconds

14 AI modules – (53 to 56 analog inputs): 2900 milliseconds

15 AI modules – (57 to 60 analog inputs): 3100 milliseconds

16 AI modules – (61 to 64 analog inputs): 3300 milliseconds

Scan rate dependent upon the number and type of configured function blocks.

Analog outputs will be updated at the same rate as analog inputs.

Fast Logic digital I/O will be serviced one time every 100 msec.

Up to four independent setpoint programs can be configured with up to 50 segments each. Up to 70 programs maximum storage.

Standard: 100 Vac to 240 Vac, 50 Hz or 60 Hz; or 100 Vdc to 240 Vdc

Fuse: 3.15 A T 250v, or equivalent.

Optional: 24 V dc or ac, 50 Hz or 60 Hz

Fuse: 6.3 A slow blow, or equivalent.

100 VA maximum

Lithium: Tadiran TL5101/SPD ½ AA, 3.6 Vdc

Removable terminal blocks with cross-slotted screw terminals; accepts 16 AWG to 22 AWG.

Two ports for external connections –

CONFIGURATION: RS232 port dedicated connection of the controller to a PC running the Control Builder Configuration software.

DISPLAY: RS422 port dedicated connection to the Operator Interface.

Optional: Two RS 485 Serial Communication ports, Modbus® RTU Protocol, Ethernet protocol.

Connection: Twisted pair with shield.

Distance: 600 meters, (2000 feet)

Communication mode: Half duplex

Number of devices/link: COMM A: 31, COMM B: 16

Baud Rates: 9600, 19200, 38400

Release F

UMC800 Controller Installation and User Guide

97

4/01

 

 

Page 105
Image 105
Honeywell UMC800 manual Design