Connecting AC Power to a Dual-SP Storage System

15

Before You Start

To complete this procedure, you will need

The sense cable, which is the serial cable that shipped with the UPS. This cable allows Navisphere Express to monitor UPS status.

The AC power cables appropriate to your power source. These cables shipped with the storage system.

CAUTION

You must connect the UPS serial cable to the purple UPS (+ -) port on SP A. This connection is required for write-cache operation, and allows Navisphere Express to monitor the UPS. A standard null-modem or other service serial cable may look identical to the unique serial cable supplied with the UPS, but it will not work. Be sure to use the unique serial cable that came with the UPS.

STEP 1. Plug one end of the UPS serial cable into the serial port on the UPS (Figure 43).

STEP 2. Plug the free end of the UPS serial cable into the UPS connector (labeled with a +- battery icon) on SP A (Figure 43).

OFF

O

I

ON

OFF

O

I

ON

OFF

O

I

ON

+ -

UPS Serial cable

Power Cords

OFF

O

I

ON

OFF

O

I

ON

OFF

O

I

ON

UPS

EMC3264

FIGURE 43. Connecting the UPS Serial Cable to an SSR212PP2f or SSR212PP2i

Intel Storage System SSR212PP User Guide

95

Page 109
Image 109
Intel SSR212PP manual Connecting AC Power to a Dual-SP Storage System