6: Basic Parameters

DNS Servers

#1 - #3

Configure up to three name servers. #1 is required if you choose to configure DNS (Domain Name Server) servers.

The first three DNS servers acquired via DHCP through Eth1 and/or Eth2 display automatically.

DHCP-Acquired DNS Servers

#1 - #3

Displays the IP address of the name servers if automatically assigned by DHCP.

TCP Keepalive Parameters

Start Probes

Number of seconds the SLC unit waits after the last transmission before sending the

 

first probe to determine whether a TCP session is still alive. The default is 600

 

seconds (10 minutes).

 

 

Number of Probes

Number of probes the SLC 8000 advanced console manager sends before closing a

 

session. The default is 5.

 

 

Interval

The number of seconds the SLC unit waits between probes. The default is 60

 

seconds.

 

 

3.To save your entries, click the Apply button. Apply makes the changes immediately and saves them so they will be there when the SLC 8000 advanced console manager is rebooted.

Ethernet Counters

The Network > Network Settings page displays statistics for each of the SLC Ethernet ports since boot-up. The system automatically updates them.

Note: For Ethernet statistics for a smaller time period, use the diag perfstat command.

Network Commands

The following CLI commands correspond to the web page entries described above.

To configure Ethernet port 1 or 2:

set network port <12> <parameters>

Parameters

mode <auto10mbit-half100mbit-half 10mbit-full100mbit-full1000mbit-full> state <dhcpbootpstaticdisable> [ipaddr <IP Address> mask <Mask>] [ipv6addr <IP v6 AddressPrefix>]

To configure up to three DNS servers:

set network dns <123> ipaddr <IP Address>

SLC™ 8000 Advanced Console Manager User Guide

61

Page 61
Image 61
Lantronix SLC 8000 manual DHCP-Acquired DNS Servers, TCP Keepalive Parameters, Ethernet Counters, Network Commands