SAGEM 3P@C
Table
Cable type | Laying mode | Minimum parallel | ||
|
|
| net spacing L(mm) | |
|
|
|
| |
380 V | power | Parallel laying | 130 | |
cable |
|
|
| |
| One side is placed in a grounded | 70 | ||
<2kV.A |
| |||
| metal trough or steel tube. |
| ||
|
|
|
| |
|
| Both sides are placed in a grounded | 10 | |
|
| metal trough or steel tube. |
| |
|
|
|
| |
380 V | power | Parallel laying | 300 | |
cable |
|
|
| |
| One side is placed in a grounded | 150 | ||
2 – 5kV.A | ||||
metal trough or steel tube. |
| |||
|
|
|
| |
|
| Both sides are placed in a grounded | 80 | |
|
| metal trough or steel tube. |
| |
|
|
|
| |
380 V | power | Parallel laying | 600 | |
cable |
|
|
| |
| One side is placed in a grounded | 300 | ||
>5kV.A |
| |||
| metal trough or steel tube. |
| ||
|
|
|
| |
|
| Both sides are placed in a grounded | 150 | |
|
| metal trough or steel tube. |
| |
|
|
|
|
| If the spacing length between a 380 V power cable (<2kV.A) | |
| and a Ethernet cable is not more than 10 m with both placed | |
Prompt | in a grounded trough, the minimum parallel net spacing can | |
be 10 mm. | ||
|
Table
|
| Minimum parallel | net | Minimum | net spacing |
Other pipelines |
| spacing L(mm) |
| between | crossed cable |
|
|
| and line H(mm) | ||
|
|
|
|
| |
|
| Ethernet cable |
| Ethernet cable | |
|
|
|
|
|
|
Cable | for | 1000 |
| 300 |
|
conducting |
|
|
|
|
|
lightning to | the |
|
|
|
|
ground |
|
|
|
|
|
|
|
|
|
|
|
protection |
| 50 |
| 20 |
|
grounding |
|
|
|
|
|
|
|
|
|
| |
Water supply pipe | 150 |
| 20 |
| |
|
|
|
|
|
|
Compressed | air | 150 |
| 20 |
|
pipe |
|
|
|
|
|
|
|
|
|
| |
Thermo pipe (non- | 500 |
| 500 |
| |
enveloped) |
|
|
|
|
|
|
|
|
|
|
|
Thermo | pipe | 300 |
| 300 |
|
(enveloped) |
|
|
|
|
|
|
|
|
|
|
|
Gas pipe |
| 300 |
| 20 |
|
|
|
|
|
|
|
3P@C Installation Manual