Table 5-1 Requirements of spacing between Ethernet cables and cables of other electric devices

Cable type

Laying mode

Minimum parallel

 

 

 

net spacing L(mm)

 

 

 

 

380 V

power

Parallel laying

130

cable

 

 

 

 

One side is placed in a grounded

70

<2kV.A

 

 

metal trough or steel tube.

 

 

 

 

 

 

 

Both sides are placed in a grounded

10

 

 

metal trough or steel tube.

 

 

 

 

 

380 V

power

Parallel laying

300

cable

 

 

 

 

One side is placed in a grounded

150

2 – 5kV.A

metal trough or steel tube.

 

 

 

 

 

 

 

Both sides are placed in a grounded

80

 

 

metal trough or steel tube.

 

 

 

 

 

380 V

power

Parallel laying

600

cable

 

 

 

 

One side is placed in a grounded

300

>5kV.A

 

 

metal trough or steel tube.

 

 

 

 

 

 

 

Both sides are placed in a grounded

150

 

 

metal trough or steel tube.

 

 

 

 

 

 

If the spacing length between a 380 V power cable (<2kV.A)

 

and a Ethernet cable is not more than 10 m with both placed

Prompt

in a grounded trough, the minimum parallel net spacing can

be 10 mm.

 

Table 5-2 Requirements of spacing between the Ethernet cables on the wall and other pipelines

 

 

Minimum parallel

net

Minimum

net spacing

Other pipelines

 

spacing L(mm)

 

between

crossed cable

 

 

 

and line H(mm)

 

 

 

 

 

 

 

Ethernet cable

 

Ethernet cable

 

 

 

 

 

 

Cable

for

1000

 

300

 

conducting

 

 

 

 

 

lightning to

the

 

 

 

 

ground

 

 

 

 

 

 

 

 

 

 

 

protection

 

50

 

20

 

grounding

 

 

 

 

 

 

 

 

 

 

Water supply pipe

150

 

20

 

 

 

 

 

 

 

Compressed

air

150

 

20

 

pipe

 

 

 

 

 

 

 

 

 

 

Thermo pipe (non-

500

 

500

 

enveloped)

 

 

 

 

 

 

 

 

 

 

 

Thermo

pipe

300

 

300

 

(enveloped)

 

 

 

 

 

 

 

 

 

 

 

Gas pipe

 

300

 

20

 

 

 

 

 

 

 