Figure
Bolt of the pressure plate assembly
Wire outlet
Antistatic floor
| |
| bolt (side) |
| |
bolt (middle) | Expansion bolt |
Sequence of fastening the bolts: Bolt of the pressure plate assembly ¡ú Expansion bolt
1.1.1.44Fix the cabinet
A. Level the cabinet
Restore all the antistatic floorboards to their original state. Loosen all the bolts on the pressure plate assemblies and remove the pressure plate assemblies. Push the cabinet to the predefined position (the cabinet feet must coincide with their position marks) and screw the four feet with a spanner, so that the bottom surface of the cabinet is 73 mm away from the floor and all cabinets are aligned. Place a horizontal ruler at the plane at the top of cabinet in two perpendicular directions, to check its horizontal level. Fine tune the cabinet feet so that the cabinet becomes level and then tighten the locking nuts of the cabinet feet.
B. Fix the cabinet
Put back the pressure plate assembly again, so that the pressure plate presses against the cabinet feet and use a torque wrench to fasten the pressure plate assembly bolt to 45 Nm.
Please skip Step C below to install a single cabinet.
Note
C. Cabinet top fixation
When two (or more) cabinets are combined, it is necessary to connect the combined cabinets. Figure
3P@C Installation Manual
Page | Reproduction and communication in any form prohibited without the written permission of SAGEM SA |