SAGEM 3P@C

The cabinet of 3P@C 4450E weighs about 150 kg and so two professional installers are needed to install it. The side of the rack shall not be less than 0.1 m away from the wall surface, and the back of the rack shall keep a space of more than 0.8 m from the wall surface and other equipments

Note (including the operation console chairs/desks), so as to facilitate heat dissipation and equipment maintenance. The distance between the front face of one cabinet row and that of its adjacent row should be no less than 0.8 m.

The equipment installation space is illustrated in Figure 4-2.

Figure 4-2 Equipment installation space

Inner wall or

 

 

other barriers

4-f60.0 (Feet

4-f60.0 (Feet

 

position mark)

position mark)

 

Use M12 expansion bolt

Use M12 expansion bolt

4.1.1.Installation on the Cement Floor

The 19-inch cabinet 2.2 m high is installed on the cement floor by using pressure plates to press on the feet. Since the feet have the insulating function and the pressure plate assembly contains insulating parts, the whole equipment is insulated from the earth before the grounding cable is connected and the insulating requirements can be effectively satisfied. See Figure 4-3 for the installation flow.

3P@C Installation Manual

Page 4-2Reproduction and communication in any form prohibited without the written permission of SAGEM SA