SAGEM 3P@C

Table 2-7Status definitions of the LED indicators on the front panel of ADUC

LED

Identific

Color

Status

Description

 

ation

 

 

 

ADUC

RUN

Green

On

The system is powered on

running

 

 

Off

The system is powered off or

status

 

 

 

abnormal

indicator

 

 

Flashing

The ADUC operates normally

 

ALM

Red

Off

The ADUC operates normally

 

 

 

ON

ADUC alarm

2.4.Power Distribution System

2.4.1.Overview

The DC distribution unit of 3P@C 4450E adopts the -48 V DC power supply. It is 4U high and is fixed to the upper part of the equipment rack rear. The -48 V DC input power is divided into 4 tributaries whose outputs are controlled by air switches separately. Their connection relations are shown in Figure 2-19:

Figure 2-19 Connection relations

2.4.2.Functional Features

Input requirements

1.-48 V single input.

2.-48 V input range: -36 ~ -72 V DC.

3.-48 V total input power: 3,300 W. Output requirements

1.The -48 V power is output to 4 channels that are led out by wiring terminals and controlled by air switches.

2.The rated current of the air switch is 32 A.

3P@C Installation Manual

Page 2-14

Reproduction and communication in any form prohibited without the written permission of SAGEM SA