4220 Flow Meter
Section 2 Programming
If you select LEOPOLD-LAGCO, this will appear:
• 4" • • 6" • • 8" • • 10" • • 12" • • 15" • • 18" • • 21" •
If you press the right arrow key several times, the sizes shown below will move onto the screen:
• 24" • • 30" •
If you select HS, the following display will appear:
HS FLUME SIZE
• 0.4' • • 0.5' • • 0.6' • • 0.8' • • 1.0' •
If you select H, the following will appear:
H FLUME SIZE
• 5' • • .75' • • 1' • • 2' • • 2.5' • • 3' • • 4.5' •
If you select HL, the following will appear:
HL FLUME SIZE
• 2.0' • • 2.5' • • 3.0' • • 3.5' • • 4.0' •
If you select TRAPEZOIDAL, this will appear:
TRAPEZOIDAL SIZE
• LG 60 V • • 2" 45 WSC • • 12” 45 SRCRC •
This completes the section on WEIR/FLUME flow conversions.
Returning to Step 2, SELECT FLOW CONVERSION: If you select EQUATION the following will appear:
ENTER EQUATION UNITS
Q= XXX.XXXH^X.XX + XXX.XXXH^X.XX
This step allows you to enter an equation that is appropriate for your flow situation. The equation is expressed in the general form of Q = k1HP1 + k2HP2, where Q = flow rate, k1 = a constant, H = level or head, and P1 is the power to which H is raised. k2 and P2 are a second constant and power found in some equations. If your equation has only one term, you should enter 0 for the second constant.
Returning to Step 2, SELECT FLOW CONVERSION, if you select MANNING, the following will appear:
SELECT MANNING TYPE
• ROUND PIPE • •
TRAPEZOIDAL is also available, if you move to the right with the right arrow key.