4220 Flow Meter
Appendix D General Safety Procedures
D-5
“It seems unlikely that anyone has ever died in a sewer from suf-
focation, that is, a lack of oxygen. Deaths have often been
attributed to ‘asphyxiation.’ This is a word which, according to
the dictionary, is used to mean death from an atmosphere that
does not support life. The word has sometimes been misinter-
preted as meaning suffocation, which is only one kind of asphyxi-
ation.
“In nearly all cases of death in sewers, the real killer is hydrogen
sulfide. It is important that this fact be recognized. Many cities
diligently test for explosive gases, which is very important, and
they may measure the oxygen concentration which usually is
unimportant, but they rarely measure H2S. Death has occurred
where it is unlikely that there was any measurable reduction in
the oxygen concentration. Waste water containing 2 mg per liter
of dissolved sulfide, and at a pH of 7.0, can produce, in a chamber
with high turbulence, a concentration of 300 PPM H2S, in the air.
This is considered to be a lethal concentration. Many people have
died from H2S, not only in sewers and industries, but also from
swamps and from hot springs. In one resort area, at least five
persons died from H2S poisoning before the people were ready to
admit that H2S is not a therapeutic agent. Hardly a year passes
in the U.S. without a sewer fatality from H2S as well as deaths
elsewhere in the world.
“The presence of H2S in a sewer atmosphere is easily deter-
mined. A bellows-and-ampoule type of tester is very satisfactory
for the purpose, even though it is only crudely quantitative.
When using a tester of this type, do not bring the air to the
ampoule by way of a tube, as this may change the H2S concen-
tration. Hang the ampoule in the air to be tested, with a suction
tube to the bulb or bellows.
“Lead acetate paper is very useful as a qualitative indicator. It
cannot be used to estimate the amount of sulfide, but it will
quickly turn black in an atmosphere containing only a tenth of a
lethal concentration.
“Electrodes or other similar electrical indicating devices for H2S
in air have been marketed. Some of them are known to be unre-
liable, and we know of none that have proved dependable. Do not
use one unless you check it at frequent intervals against air con-
taining known H2S concentrations. A supposed safety device that
is unreliable is worse than none at all.
“Remember that the nose fails, too, when it comes to sensing
dangerous concentrations of H2S.
“Various other toxic gases have been mentioned in some publica-
tions. It is unlikely that any person has been asphyxiated in a
sewer by any of those other gases, except possibly chlorine. The
vapor of gasoline and other hydrocarbons is sometimes present in
amounts that could cause discomfort and illness, but under that
condition, the explosion hazard would be far more serious. The
explosimeter tests, as well as the sense of smell, would warn of
the danger. Pipelines in chemical plants might contain any