Part III | Model 6600 | |
|
|
|
|
|
|
|
|
|
surface. A waterproof mastic should be liberally applied to the under sur- faces of all four supporting legs of the cubicle system before placing it in position and bolting it in place.
4.1User Connections
All user connections are located around the periphery of the equipment panel (or cubicle) and are shown in the Outline Diagram.
4.1.1Electrical Power Connections
The system requires a 1 KW supply of 115 VAC,
4.1.2Compressed Air Supply
The system requires a supply of compressed air at
NOTE: The air supply must be oil free. As a precaution, however, the air pressure line should contain a filter(s) to remove any traces of oil, supplied and maintained by the customer.
4.1.3Sample Connection
The sample water input (see Flow Diagram) is connected at the manual valve input. A flowrate of 1 gallon/minute, minimum, is recommended. Maximum flow is governed by the impedance of the delivery system.
4.1.4Signal and Alarm Output Connections
Signal and alarm output connections are made inside the control unit to terminal blocks mounted on the interface board. Refer to chapter 2 of control unit part of the manual.
NOTE: Signal circuit resistance, including accessory devices, must not exceed 1000 ohms. The alarm contact circuit must not draw more than 3 amperes at 250 VAC (None inductive), or 30VDC.