Chapter 4 Parameters

 

Settings

 

Functions

 

Descriptions

 

 

19

 

Pulse frequency

 

Max. frequency Pr.01-00 is regarded as 100%.

 

 

command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-19

 

Analog Output Gain 1

 

 

 

Unit: 0.1

 

03-22

 

Analog Output Gain 2 (need to be used with EMV-APP01)

Unit: 0.1

 

03-25

 

Analog Output Gain 3 (need to be used with EMV-APP01)

Unit: 0.1

 

Control

VF

VFPG SVC

FOCPG TQRPG

Factory setting: 100.0

 

mode

 

 

 

 

 

 

 

 

 

 

Settings

0 to 200.0%

 

 

 

 

 

 

 

 

 

 

It is used to adjust the analog voltage level that terminal AFM outputs.

This parameter is set the corresponding voltage of the analog output 0.

03-20

Analog Output Value in REV Direction 1

 

 

03-23

Analog Output Value in REV Direction 2

 

 

03-26

Analog Output Value in REV Direction 3

 

 

Control

VF

VFPG

SVC FOCPG TQRPG

Factory setting: 0

 

mode

 

 

 

 

 

 

 

 

 

 

Settings

0

 

Absolute value in REV direction

 

 

 

 

1

 

Output 0V in REV direction

 

 

 

 

2

 

Enable output voltage in REV direction

 

 

 

 

 

 

 

 

 

 

10V( 20mA)

 

 

 

10V( 20mA)

 

 

10V( 20mA)

 

 

 

 

 

03-18

 

 

 

 

 

 

 

 

 

 

 

 

03-21

 

 

 

 

 

 

 

 

 

 

 

0V

 

 

 

0V

F requenc y

 

 

5V F requenc y

 

03-24

 

 

 

 

 

 

( 0mA)

 

 

 

 

( 0mA)

 

 

 

 

( 12mA)

03-20=0

 

03-20=1

 

 

03-20=2

 

03-23=0

 

03-23=1

 

 

03-23=2

 

03-26=0

 

03-26=1

 

 

03-26=2

 

Selections for the analog output dir ec ti on

4-84

Revision August 2008, 03VE, SW V2.04