Chapter 4 Parameters

Pr.

Explanation

Settings

Factory

VF

VFPG

SVC

FOCPG

TQRPG

 

 

 

Setting

 

 

 

 

 

02-35

Multi-function Output 5 (MO3)

33: Zero speed (actual output

 

 

 

frequency)

 

 

 

 

 

 

 

Multi-function Output 6 (MO4)

 

 

 

 

 

 

02-36

34: Zero speed with Stop (actual output

 

 

 

frequency)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02-37

Multi-function Output 7 (MO5)

35: Error output selection 1 (Pr.06-23)

 

Multi-function Output 8 (MO6)

 

 

 

 

 

 

 

02-38

36: Error output selection 2 (Pr.06-24)

 

Multi-function Output 9 (MO7)

 

 

 

 

 

 

 

02-39

37: Error output selection 3 (Pr.06-25)

 

Multi-function Output 10 (MO8)

 

 

 

 

 

 

 

02-40

38: Error output selection 4 (Pr.06-26)

 

Multi-function Output 11 (MO9)

 

 

 

 

 

 

 

02-41

39: Position attained (Pr.10-19)

 

 

 

 

 

Multi-function Output 12 (MOA)

 

 

 

 

 

 

 

02-42

40: Speed attained (including zero

 

 

 

speed)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41: Multi-position attained

 

 

 

 

 

 

 

42: Crane function

 

 

 

 

 

 

 

 

 

 

 

Group 3 Analog Input/Output Parameters

In version 2.02, the parameters are from Pr.03-00 to Pr.03-20. The settings for Pr.03-00 to Pr.03-02 are from 0 to 10

Pr.

 

Explanation

Settings

Factory

VF

VFPG

SVC

FOCPG

TQRPG

 

 

 

 

Setting

 

 

 

 

 

03-00

Analog Input 1 (AVI)

2: torque command (torque limit under

0

 

 

 

 

 

 

speed mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3: Torque compensation command

 

 

Analog Input 2 (ACI)

 

 

 

 

 

 

 

03-01

4: PID target value (refer to group 8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5: PID feedback signal (refer to group

 

 

 

Analog Input

3 (AUI)

8)

 

 

 

 

 

 

03-02

6: P.T.C. thermistor input value

 

 

 

 

 

 

 

 

 

 

 

 

 

7: Positive torque limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8: Negative torque limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9: Regenerative torque limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10: Positive/negative torque limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-20

Analog Output Value in REV Direction

0: Absolute value in REV direction

0

 

 

1: Output 0V in REV direction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2: Enable output voltage in REV

 

 

 

 

 

 

 

 

 

direction

 

 

 

 

 

 

Group 6 Protection Parameters

In version 2.02, the parameters are from Pr.06-00 to Pr.06-31. The settings of Pr.06-01 are shown as follows. The settings for Pr.06-17 to Pr.06-22 are from 0 to 62.

 

Pr.

Explanation

Settings

Factory

VF

VFPG

SVC

FOCPG

TQRPG

 

 

 

 

Setting

 

 

 

 

 

06-01

Over-voltage Stall Prevention

0.0: Disable

 

 

 

 

 

 

 

350.0~450.0Vdc

380.0

 

 

 

 

 

 

700.0~900.0Vdc

760.0

 

06-17

Present Fault Record

0: No fault

0

 

06-18

Second Most Recent Fault Record

1: Over-current during acceleration

0

 

06-19

Third Most Recent Fault Record

(ocA)

0

2: Over-current during deceleration

06-20

Fourth Most Recent Fault Record

0

(ocd)

 

06-21

Fifth Most Recent Fault Record

3: Over-current during constant speed

0

 

06-22

Sixth Most Recent Fault Record

(ocn)

0

Revision August 2008, 03VE, SW V2.04

4-27

Page 76
Image 76