Delta Electronics VFD-VE Series manual Visual, aural inspection and smell Or peculiar smell

Models: VFD-VE Series

1 291
Download 291 pages 55.35 Kb
Page 235
Image 235

Chapter 6 Fault Code Information and Maintenance „ DC capacity of main circuit

 

 

 

Maintenance

 

Check Items

Methods and Criterion

 

Period

 

 

Daily

Half

One

 

 

 

 

 

 

Year

Year

 

 

 

 

 

 

 

If there is any leak of liquid,

 

 

 

 

 

color change, crack or

Visual inspection

{

 

 

 

deformation

 

 

 

 

 

Measure static capacity when

Static capacity initial value X 0.85

 

{

 

 

required

 

 

 

 

 

 

 

 

 

 

 

 

 

„ Resistor of main circuit

 

 

 

 

 

 

 

Maintenance

 

Check Items

Methods and Criterion

 

Period

 

 

Daily

Half

One

 

 

 

 

 

 

Year

Year

 

 

 

 

 

 

 

If there is any peculiar smell or

Visual inspection, smell

 

{

 

 

insulator cracks due to overheat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Visual inspection or measure with

 

 

 

 

If there is any disconnection

multimeter after removing wiring

 

{

 

 

between +1/+2 ~ -

 

 

 

 

 

 

 

 

 

Resistor value should be within ± 10%

 

 

 

„Transformer and reactor of main circuit

 

 

Maintenance

Check Items

Methods and Criterion

 

Period

 

Daily

Half

One

 

 

 

 

Year

Year

 

 

 

 

 

If there is any abnormal vibration

Visual, aural inspection and smell

 

{

 

or peculiar smell

 

 

 

 

 

 

 

 

 

 

 

„Magnetic contactor and relay of main circuit

 

 

Maintenance

Check Items

Methods and Criterion

 

Period

 

Daily

Half

One

 

 

 

 

Year

Year

 

 

 

 

 

If there are any loose screws

Visual and aural inspection

{

 

 

 

 

 

 

 

If the contact works correctly

Visual inspection

{

 

 

 

 

 

 

 

6-10

Revision August 2008, 03VE, SW V2.04

Page 235
Image 235
Delta Electronics VFD-VE Series manual Visual, aural inspection and smell Or peculiar smell