Chapter 2 Installation and Wiring

General

„Keep control wiring as far as possible from the power wiring and in separate conduits to avoid interference. If necessary let them cross only at 90º angle.

„The AC motor drive control wiring should be properly installed and not touch any live power wiring or terminals.

NOTE

„If a filter is required for reducing EMI (Electro Magnetic Interference), install it as close as possible to AC drive. EMI can also be reduced by lowering the Carrier Frequency.

„When using a GFCI (Ground Fault Circuit Interrupter), select a current sensor with sensitivity of 200mA, and not less than 0.1-second detection time to avoid nuisance tripping.

DANGER!

Damaged insulation of wiring may cause personal injury or damage to circuits/equipment if it comes in contact with high voltage.

The specification for the control terminals

The Position of the Control Terminals

MRA RA RC

MCM +24V FWD MI1 MI3 MI5 DFM +10V AVI ACM

MRC RB

MO1 MO2 DCM REV MI2 MI4 MI6 AFM AUI ACI

Frame

Torque

Wire

B, C, D, E, E1

8 kgf-cm (6.9 in-lbf)

22-14 AWG (0.3-2.1mm2)

NOTE

Frame B: VFD007V23A/43A-2, VFD015V23A/43A-2, VFD022V23A/43A-2, VFD037V23A/43A-2;

Frame C: VFD055V23A/43A-2, VFD075V23A/43A-2, VFD110V43B-2,

Frame D: VFD110V23A/43A-2, VFD150V23A/43A-2, VFD185V23A/43A-2, VFD220V23A/43A-2

Frame E: VFD300V43A-2, VFD370V43A-2, VFD450V43A-2

Frame E1: VFD300V23A-2, VFD370V23A-2, VFD550V43C-2, VFD750V43C-2

Revision August 2008, 03VE, SW V2.04

2-15