Delta Electronics VFD-VE Series manual 06-23, 06-24, 06-25, 06-26

Models: VFD-VE Series

1 291
Download 291 pages 55.35 Kb
Page 151
Image 151

Chapter 4 Parameters

 

 

Settings

 

Control Mode

 

 

 

 

 

VF

VFPG

SVC

FOCPG

TQRPG

 

 

 

52: Password error (PcodE)

 

 

53: Reserved

 

 

 

 

 

 

 

 

54: Communication error (cE1)

 

 

55: Communication error (cE2)

 

 

56: Communication error (cE3)

 

 

57: Communication error (cE4)

 

 

58: Communication Time-out (cE10)

 

 

59: PU time-out (cP10)

 

 

60: Brake transistor error (bF)

 

 

61: Y-connection/Δ-connection switch error (ydc)

 

 

 

 

62: Decel. Energy Backup Error (dEb)

 

 

63: Slip error (oSL)

 

 

 

 

64: Broken belt error (bEb)

 

 

65: Error PID feedback signal of tension (tdEv)

It will record when the fault occurs and force stopping. For the Lv, it will record when it is operation, or it will warn without record.

Setting 62: when DEB function is enabled, the drive will execute DEB and record to the Pr.06- 17 to Pr.06-22 simultaneously.

 

06-23

Fault Output Option 1

 

 

Unit: 1

06-24

Fault Output Option 2

 

 

Unit: 1

 

06-25

Fault Output Option 3

 

 

Unit: 1

 

06-26

Fault Output Option 4

 

 

Unit: 1

 

Control

VF

VFPG SVC

FOCPG TQRPG

Factory Setting: 0

 

mode

 

 

 

 

 

 

 

 

 

Settings

0 to 65535 sec (refer to bit table for fault code)

 

 

 

 

 

 

 

 

These parameters can be used with multi-function output (set Pr.02-11 to Pr.02-14 to 35-38) for the specific requirement. When the fault occurs, the corresponding terminals will be activated (It needs to convert binary value to decimal value to fill in Pr.06-23 to Pr.06-26).

 

 

Fault code

Bit0

Bit1

Bit2

Bit3

Bit4

Bit5

Bit6

 

 

current

Volt.

OL

SYS

FBK

EXI

CE

 

 

 

 

 

 

 

0: No fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1: Over-current during acceleration

 

 

 

 

 

 

 

 

 

(ocA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2: Over-current during deceleration

 

 

 

 

 

 

 

 

 

(ocd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3: Over-current during constant

 

 

 

 

 

 

 

 

 

speed (ocn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-102

Revision August 2008, 03VE, SW V2.04

Page 151
Image 151
Delta Electronics VFD-VE Series 06-23, 06-24, 06-25, 06-26, Fault code Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Current Volt

VFD-VE Series specifications

Delta Electronics VFD-VE Series is a state-of-the-art variable frequency drive (VFD) designed to enhance energy efficiency and improve the operational capabilities of various industrial applications. Renowned for its reliability and performance, the VFD-VE Series serves a diverse range of sectors including manufacturing, HVAC, and water treatment.

One of the primary features of the VFD-VE Series is its advanced control algorithms, which provide precise speed and torque control for AC motors. The series utilizes a vector control method that enables excellent dynamic response and a wide speed range. This is particularly beneficial for applications requiring variable speeds or precise positioning, as it ensures smooth acceleration and deceleration while maintaining optimal performance.

The VFD-VE Series stands out with its Energy Saving Technology. By intelligently optimizing motor control parameters based on the load, the VFD can significantly reduce energy consumption. This built-in functionality not only helps companies save on electricity costs but also contributes to a lower carbon footprint, aligning with global sustainability efforts.

Another key characteristic of the VFD-VE Series is its user-friendly interface. Equipped with a clear and intuitive LCD display, it simplifies monitoring and adjustments, allowing operators to configure settings easily. Additionally, the series supports various communication protocols such as Modbus, EtherCAT, and CANopen, enabling seamless integration with existing control systems for enhanced automation.

The VFD-VE Series is built to withstand harsh industrial environments. Its robust design includes features such as IP20 or IP55 ingress protection ratings, ensuring reliable operation even in dusty or humid conditions. Furthermore, the drives are equipped with advanced thermal management systems that prevent overheating, thereby prolonging the lifespan of the equipment.

Safety is also a priority in the VFD-VE Series, which incorporates multiple safety features such as overvoltage, undervoltage, and overcurrent protection. These safeguards help protect both the drive itself and the connected machinery, minimizing downtime and reducing maintenance costs.

Overall, Delta Electronics VFD-VE Series combines cutting-edge technology, energy efficiency, and robust design to meet the dynamic needs of modern industrial automation. With its advanced features and reliable performance, it is an ideal choice for businesses aiming to optimize their processes and achieve greater energy savings.