Chapter 4 Parameters

free run status

output

 

frequency

 

Y-connection output

ON

Pr.02-11~14=31

Y-connection

 

confirmation input

ON

Pr.02-01~06=29

 

-connection output

ON

Pr.02-11~14=32

 

-connection

 

confirmation input

 

Pr.02-01~06=30

 

Y-switch error

ON

frequency

2 seconds

 

 

delay time

 

Pr.05-30

05-13

Full-load Current of Motor 2

Unit: 1%

Control

VF

VFPG SVC FOCPG TQRPG

Factory setting: #.##

mode

 

 

 

 

 

Settings

40 to 100%

 

This value should be set according to the rated frequency of the motor as indicated on the motor nameplate. The factory setting is 90% X rated current.

Example: The rated current for 7.5HP (5.5kW) is 25 and factory setting is 22.5A. The range for setting will be 10~30A.(25*40%=10 and 25*120%=30)

 

05-14

Rated Power of Motor 2

Unit: 0.01

 

 

 

 

 

 

Control

SVC

FOCPG TQRPG

Factory setting: #.##

 

mode

 

 

 

 

 

 

 

Settings

0 to 655.35

 

 

 

 

It is used to set rated power of the motor 2. The factory setting is the power of the drive.

 

 

 

05-15

Rated Speed of Motor 2 (rpm)

Unit: 1

 

Control

VFPG

SVC FOCPG TQRPG

Factory setting: 1710

 

mode

 

 

 

 

 

 

 

Settings

0 to 65535

 

It is used to set the rated speed of the motor and need to set according to the value indicated on the motor nameplate.

Revision August 2008, 03VE, SW V2.04