Chapter 4 Parameters

When integral time is set to 0, it is disabled. Pr.10-08 defines the switch frequency for the

ASR1 (Pr.10-04, Pr.10-05) and ASR2 (Pr.10-06, Pr.10-07).

PI

10-06

10-07

10-04

10-05

10-21

10-22

5Hz

 

5Hz

 

 

 

0Hz

10-08

Hz

 

When using multi-function input terminals to switch ASR1/ASR2, the diagram will be shown as follows.

Setting multi-function input terminal to 27

(ASR1/ASR2 switch)

ON

OFF

OFF

ASR 1

 

ASR 2

 

ASR 1

 

 

 

 

 

 

 

 

 

 

 

0.1 sec

0.1 sec

 

10-09

ASR Primary Low Pass Filter Gain

 

Control

FOCPG

 

 

mode

 

 

 

 

Settings

0.000 to 0.350 sec

 

It defines the filter time of the ASR command.

 

 

 

10-10

PG Stall Level

 

Control

VFPG FOCPG

 

 

mode

 

 

 

 

 

 

Settings

0 to 120% (0: disable)

This parameter determines the maximum PG feedback signal allowed (max. output frequency Pr.01-00 =100%)

10-11PG Stall Detection Time

Control VFPG FOCPG mode

Unit: 0.001 Factory Setting: 0.008

Unit: 1 Factory Setting: 115

before a fault occurs.

Unit: 0.1 Factory Setting: 0.1

 

 

Settings

0.0 to 2.0 sec

 

 

 

 

 

 

10-12

PG Slip Range

Unit: 1

 

Control

VFPG FOCPG

 

Factory Setting: 50

 

mode

 

 

 

 

 

 

4-152

Revision August 2008, 03VE, SW V2.04