Chapter 4 Parameters

 

Group 1 Basic Parameters

 

 

 

 

 

 

01-00

Maximum Output Frequency

Unit: 0.01

 

 

 

 

 

 

 

Control

VF

VFPG

SVC FOCPG TQRPG

Factory setting: 60.00/50.00

 

mode

 

 

 

 

 

 

 

 

Settings

 

50.0 to 600.00Hz

 

 

 

 

 

 

 

This parameter determines the AC motor drive’s Maximum Output Frequency. All the AC motor drive frequency command sources (analog inputs 0 to +10V, 4 to 20mA and -10V to +10V) are scaled to correspond to the output frequency range.

01-01

1st Output Frequency Setting 1

 

 

01-35

1st Output Frequency Setting 2

Unit: 0.01

 

Control

VF

VFPG

SVC FOCPG TQRPG

Factory setting: 60.00/50.00

 

mode

 

 

 

 

 

 

 

 

Settings

 

0.00~600.00Hz

 

 

 

 

 

 

 

These are for the base frequency and motor rated frequency.

This value should be set according to the rated frequency of the motor as indicated on the motor nameplate. If the motor is 60Hz, the setting should be 60Hz. If the motor is 50Hz, it should be set to 50Hz.

Pr.01-35 is used for the application occasion that uses double base motor.

 

01-02

1st Output Voltage Setting 1

 

 

01-36

1st Output Voltage Setting 2

Unit: 0.1

 

Control

VF

VFPG SVC

FOCPG TQRPG

 

 

mode

 

 

 

 

 

 

 

 

Settings

230V series

0.1 to 255.0V

Factory Setting: 220.0

 

 

 

460V series

0.1 to 510.0V

Factory Setting: 440.0

 

 

 

 

 

 

These are for the base frequency and motor rated frequency.

This value should be set according to the rated voltage of the motor as indicated on the motor nameplate. If the motor is 220V, the setting should be 220.0. If the motor is 200V, it should be set to 200.0.

There are many motor types in the market and the power system for each country is also difference. The economic and convenience method to solve this problem is to install the AC motor drive. There is no problem to use with the different voltage and frequency and also can amplify the original characteristic and life of the motor.

01-03

2nd Output Frequency Setting 1

Unit: 0.01

4-50