Chapter 5 Troubleshooting

5.9 Motor cannot Run

Motor cannot run

Reset after clearing fault and then RUN

Check if CE01

No

displays

normally

 

 

Yes

 

 

 

 

Check if there is any fault code displayed

No

Check if non-fuse breaker and magnetic contactor are ON

 

Yes

 

Check if input

No

voltage is normal

 

 

Yes

 

 

 

 

 

 

No Set them to ON

Check if any faults occur, such as Lv, PHL or disconnection

It can run when no faults occur

Input "RUN"

No

If jumper or DC

No

Use jumper

reactor is connected

command

 

 

 

 

or DC reactor

 

 

 

 

 

 

between +1 and +2/B1

 

 

by keypad

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

Press RUN key to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

check if it can run

 

 

 

 

 

 

 

 

 

Maybe AC motor drive has malfunction or misoperation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

due to noise. Please contact DELTA.

 

 

 

 

Press UP key to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

set frequency

 

 

No Check if input FWD

 

No Check if the wiring

Yes

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or REV command

 

 

 

 

 

of terminal FWD

 

 

 

Change switch or relay

 

 

Press UP to

 

 

 

 

 

 

 

 

 

and between

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REV-DCM is correct

 

 

 

 

 

 

 

check if motor

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

can run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

No

No Set frequency or not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Correct connection

 

 

 

 

 

 

 

 

 

Modify frequency

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting

 

 

 

 

if upper bound freq.

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and setting freq. is

 

 

 

 

 

 

 

Check if the parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lower than the min.

 

 

 

 

 

 

 

setting and wiring of

 

 

Yes

Change defective

 

 

 

 

 

 

 

 

 

 

 

 

output freq.

 

 

 

 

 

 

 

analog signal and

 

 

 

potentiometer and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

multi-step speed

 

 

 

relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

are correct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check if there is any

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor has malfunction

 

 

 

 

 

No

 

Maybe AC motor drive has malfunction.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output voltage from

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

terminals U, V and W

 

Please contact DELTA.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If load is too large

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check if motor

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check if the setting

 

 

 

 

 

 

connection

 

 

 

 

Connect correctly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

is correct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of torque

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

compensation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is correct

 

 

 

 

 

 

 

Motor is locked due to large load, please reduce load.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

For example, if there is a brake, check if it is released.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Increase the setting of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

torque compensation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5-6

Revision August 2008, 03VE, SW V2.04

Page 221
Image 221
Delta Electronics VFD-VE Series manual Motor cannot Run

VFD-VE Series specifications

Delta Electronics VFD-VE Series is a state-of-the-art variable frequency drive (VFD) designed to enhance energy efficiency and improve the operational capabilities of various industrial applications. Renowned for its reliability and performance, the VFD-VE Series serves a diverse range of sectors including manufacturing, HVAC, and water treatment.

One of the primary features of the VFD-VE Series is its advanced control algorithms, which provide precise speed and torque control for AC motors. The series utilizes a vector control method that enables excellent dynamic response and a wide speed range. This is particularly beneficial for applications requiring variable speeds or precise positioning, as it ensures smooth acceleration and deceleration while maintaining optimal performance.

The VFD-VE Series stands out with its Energy Saving Technology. By intelligently optimizing motor control parameters based on the load, the VFD can significantly reduce energy consumption. This built-in functionality not only helps companies save on electricity costs but also contributes to a lower carbon footprint, aligning with global sustainability efforts.

Another key characteristic of the VFD-VE Series is its user-friendly interface. Equipped with a clear and intuitive LCD display, it simplifies monitoring and adjustments, allowing operators to configure settings easily. Additionally, the series supports various communication protocols such as Modbus, EtherCAT, and CANopen, enabling seamless integration with existing control systems for enhanced automation.

The VFD-VE Series is built to withstand harsh industrial environments. Its robust design includes features such as IP20 or IP55 ingress protection ratings, ensuring reliable operation even in dusty or humid conditions. Furthermore, the drives are equipped with advanced thermal management systems that prevent overheating, thereby prolonging the lifespan of the equipment.

Safety is also a priority in the VFD-VE Series, which incorporates multiple safety features such as overvoltage, undervoltage, and overcurrent protection. These safeguards help protect both the drive itself and the connected machinery, minimizing downtime and reducing maintenance costs.

Overall, Delta Electronics VFD-VE Series combines cutting-edge technology, energy efficiency, and robust design to meet the dynamic needs of modern industrial automation. With its advanced features and reliable performance, it is an ideal choice for businesses aiming to optimize their processes and achieve greater energy savings.