current

 

 

 

 

Chapter 4 Parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5%

 

 

 

Pr.06-07,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.06-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.06-08, 06-11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06-12

Current Limit

 

 

 

 

 

 

 

 

 

 

 

 

Unit: 1

 

Control

FOCPG

TQRPG

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting: 150

 

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Settings

 

0 to 250%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

It is used to set the current limit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06-13

Electronic Thermal Relay Selection (Motor 1)

 

 

 

 

 

 

 

 

Control

VF

VFPG

SVC FOCPG TQRPG

 

 

 

 

 

 

Factory Setting: 2

 

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Settings

0

 

 

Operate with a Inverter Motor (forced external cooling)

1Operate with a Standard Motor (self-cooled by fan)

2Disabled

06-27Electronic Thermal Relay Selection (Motor 2)

Control

VF

VFPG

SVC FOCPG TQRPG

Factory Setting: 2

mode

 

 

 

 

 

 

Settings

0

Operate with a Inverter Motor (forced external cooling)

 

 

1

Operate with a Standard Motor (self-cooled by fan)

 

 

2

Disabled

 

 

 

 

 

 

It is used to prevent self-cooled motor overheats under low speed. User can use electrical thermal relay to limit driver’s output power.

 

06-14

Electronic Thermal Characteristic for Motor 1

Unit: 0.1

 

Control

VF

VFPG

SVC

FOCPG TQRPG

Factory Setting: 60.0

 

mode

 

 

 

 

 

 

 

 

 

Settings

 

30.0 to 600.0 sec

 

 

 

 

 

06-28

Electronic Thermal Characteristic for Motor 2

Unit: 0.1

 

Control

VF

VFPG

SVC

FOCPG TQRPG

Factory Setting: 60.0

 

mode

 

 

 

 

 

 

 

 

 

Settings

 

30.0 to 600.0 sec

 

 

 

 

 

 

 

 

Revision August 2008, 03VE, SW V2.04

4-99