Chapter 4 Parameters

 

 

 

 

 

07-10

Base Block Speed Search

 

 

Control

VF

VFPG

SVC FOCPG TQRPG

Factory Setting: 0

 

mode

 

 

 

 

 

 

 

 

Settings

0

Stop operation

 

 

 

 

1

Speed search starts with last frequency command

 

 

 

2

Speed search starts with minimum output frequency

 

 

 

 

 

 

This parameter determines the AC motor drive restart method after External Base Block is enabled.

In PG control mode, the AC motor drive will execute the speed search function automatically by the PG speed when this setting isn’t set to 0.

 

07-11

Auto Restart After Fault

Unit: 1

 

Control

VF

VFPG SVC FOCPG TQRPG

Factory Setting: 0

 

mode

 

 

 

 

 

 

 

Settings

0 to 10

 

 

 

 

 

 

Only after an over-current OC or over-voltage OV fault occurs, the AC motor drive can be reset/restarted automatically up to 10 times.

Setting this parameter to 0 will disable the reset/restart operation after any fault has occurred. When enabled, the AC motor drive will restart with speed search, which starts at the frequency before the fault. To set the waiting time before restart after a fault, please set Pr. 07-08 Base Block Time for Speed Search.

07-12

Speed Search during Start-up

 

Control

VF

VFPG SVC FOCPG TQRPG

Factory Setting: 0

mode

 

 

 

 

Settings 0 Disable

1Speed search from maximum frequency

2Speed search from start-up frequency

3Speed search from minimum frequency

This parameter is used for starting and stopping a motor with high inertia. A motor with high inertia will take a long time to stop completely. By setting this parameter, the user does not need to wait for the motor to come to a complete stop before restarting the AC motor drive. If a PG card and encoder is used on the drive and motor, then the speed search will start from the speed that is detected by the encoder and accelerate quickly to the commanded frequency. The output current is set by the Pr.07-09.

Revision August 2008, 03VE, SW V2.04