Chapter 2 Installation and Wiring

Terminal

Terminal Function

 

Factory Settings (SINK)

Symbol

 

 

ON: Connect to DCM

 

 

 

 

Analog output meter

Impedance:

 

18.5kΩ (voltage output)

 

 

 

1.1mΩ (current output)

 

 

 

 

 

 

Output current

20mA max

AFM

 

Resolution:

 

max. frequency corresponds to

 

 

 

0-10V

 

AFM

Range:

 

0 ~ 10V/0 ~ 20mA

 

Function:

 

Pr.03-18

 

0~20mA

 

 

Switch:

 

AFM switch, factory setting is 0-

 

ACM

 

 

 

 

10V

 

 

 

 

ACM

Analog control signal

Common for AVI, ACI, AUI, AFM

(common)

 

 

 

 

*Control signal wiring size: 18 AWG (0.75 mm2) with shielded wire.

Analog input terminals (AVI, ACI, AUI, ACM)

„Analog input signals are easily affected by external noise. Use shielded wiring and keep it as short as possible (<20m) with proper grounding. If the noise is inductive, connecting the shield to terminal ACM can bring improvement.

„If the analog input signals are affected by noise from the AC motor drive, please connect a capacitor and ferrite core as indicated in the following diagrams:

AVI/ACI/AUI

C

ACM

ferrite core

wind each wires 3 times or more around the core Digital inputs (FWD, REV, MI1~MI6, DCM)

„When using contacts or switches to control the digital inputs, please use high quality components to avoid contact bounce.

Digital outputs (MO1, MO2, MCM)

„Make sure to connect the digital outputs to the right polarity, see wiring diagrams.

„When connecting a relay to the digital outputs, connect a surge absorber or fly-back diode across the coil and check the polarity.