Chapter 4 Parameters

Group 3 Analog Input/Output Parameters

 

Pr.

Explanation

Settings

Factory

VF

VFPG

SVC

FOCPG

TQRPG

 

 

 

 

Setting

 

 

 

 

 

03-00

Analog Input 1 (AVI)

0: No function

1

 

 

 

 

 

 

 

 

03-01

Analog Input 2 (ACI)

1: Frequency command (torque limit under TQR control

0

 

mode)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-02

Analog Input 3 (AUI)

2: torque command (torque limit under speed mode)

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3: Torque compensation command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4: PID target value (refer to group 8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5: PID feedback signal (refer to group 8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6: P.T.C. thermistor input value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7: Positive torque limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8: Negative torque limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9: Regenerative torque limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10: Positive/negative torque limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11: PID feedback signal of tension

 

 

 

 

12: Line speed

 

 

 

 

13: Reel diameter

 

 

 

 

14: PID target value of tension (tension closed-loop)

 

 

 

 

15: Tension setting (tension open-loop)

 

 

 

 

 

 

 

 

16: Zero-speed tension

 

 

 

 

 

 

 

 

17: Tension taper

 

 

 

 

 

03-03

Analog Input Bias 1

-100.0~100.0%

0

(AVI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-04

Analog Input Bias 2

-100.0~100.0%

0

(ACI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-05

Analog Input Bias 3

-100.0~100.0%

0

(AUI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-06

Positive/negative Bias

0: Zero bias

0

Mode (AVI)

1: Lower than bias=bias

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-07

Positive/negative Bias

2: Greater than bias=bias

0

Mode (ACI)

3: The absolute value of the bias voltage while serving

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-08

Positive/negative Bias

as the center

0

Mode (AUI)

4: Serve bias as the center

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-09

Analog Input Gain 1

-500.0~500.0%

100.0

(AVI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-10

Analog Input Gain 2

-500.0~500.0%

100.0

(ACI )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-11

Analog Input Gain 3

-500.0~500.0%

100.0

(AUI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-12

ACI/AVI2 Selection

0: ACI

0

 

1: AVI 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-13

Analog Input Delay

0.00~2.00 sec

0.01

Time (AVI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-14

Analog Input Delay

0.00~2.00 sec

0.01

Time (ACI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-15

Analog Input Delay

0.00~2.00 sec

0.01

Time (AUI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-16

Addition Function of

0: Disable (AVI, ACI, AUI)

 

the Analog Input

1: Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03-17

Loss of the ACI Signal

0: Disable

0

 

1: Continue operation at the last frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2: Decelerate to stop

 

 

 

 

 

 

 

 

 

3: Stop immediately and display E.F.

 

 

 

 

 

 

03-18

Analog Output

0: Output frequency (Hz)

0

Selection 1

1: Frequency command (Hz)

 

 

 

 

03-21

Analog Output

2: Motor speed (Hz)

 

Selection 2

3: Output current (rms)

 

 

 

 

03-24

Analog Output

4: Output voltage

 

Selection 3

5: DC Bus Voltage

 

 

 

 

 

 

 

6: Power factor

 

 

 

 

7: Power

 

 

 

 

8: Output torque

 

Revision August 2008, 03VE, SW V2.04