In PG control mode, the AC motor drive will execute the speed search function automatically by the PG speed when this setting isn’t set to 0.

07-13

Decel. Time Selection for Momentary Power Loss (DEB function)

 

Control

VF

VFPG SVC FOCPG TQRPG

Factory Setting: 0

mode

 

 

 

 

Settings 0 Disable

11st decel. time

22nd decel. time

33rd decel. time

44th decel. time

5Current decel. time

6Auto decel. time

This parameter is used for the decel. time selection for momentary power loss.

 

07-14

DEB Return Time

 

Unit: 0.1

 

Control

VF

VFPG SVC

FOCPG

Factory Setting: 0.0

 

mode

 

 

 

 

 

 

 

 

Settings

0.0 to 25.0 sec

 

 

 

 

 

 

 

The DEB (Deceleration Energy Backup) function is the AC motor drive decelerates to stop after momentary power loss. When the momentary power loss occurs, this function can be used for the motor to decelerate to 0 speed with deceleration stop method. When the power is on again, motor will run again after DEB return time.

Status 1: Insufficient power supply due to momentary power-loss/unstable power (due to low voltage)/sudden heavy-load

4-112

Revision August 2008, 03VE, SW V2.04